Natural Gas Generators

Are those galvanized fittings for a gas line? Not recommended if they are. Nice gen though.
Galvanized pipe is perfect approved for above ground piping. Underground the preferred choice is PE, or coated black schedule 40 steel pipe with cathodic protection installed. Go check every natural gas meter setup and you will see galvanized piping. (A retired natural gas corrosion specialist/ district engineer/ operations manager).
 
Galvanized pipe is perfect approved for above ground piping. Underground the preferred choice is PE, or coated black schedule 40 steel pipe with cathodic protection installed. Go check every natural gas meter setup and you will see galvanized piping. (A retired natural gas corrosion specialist/ district engineer/ operations manager).
Yup. I also have galvanized pipe outside on my generator. Paint will protect it from rust
 
Yup. I also have galvanized pipe outside on my generator. Paint will protect it from rust
Paint galvanized can prolong the life of the zinc coating, which by the way is a sacrificial metal that protects the underlying steel by generating a negative voltage (cathodic) to prevent corrosion.
 
Yep its galvanized and I wish it wasn't! A pain to paint for sure
 
Very interesting, can I spray that on top of existing paint do you think?
 
Very interesting, can I spray that on top of existing paint do you think?
It works best directly on galvanized steel, then next on bare steel; can be applied over existing paint or coating if it is adhered well and shows no signs of peeling or flaking BUT not the best choice.
Inorganic zinc-rich paint seems more durable than organic in most applications. More here:


 
Last edited:
  • Like
Reactions: biggen